PCP #21046 · Lanxess Corporation · Antimicrobial
Liquid concentrate microbiocide containing 15% glutaraldehyde for control of bacteria (including slime-forming and sulfate-reducing bacteria), fungi, yeast, and algae in industrial water treatment systems including paper mills, cooling systems, oil and gas operations, and wastewater systems.
Crop × pest × application rate combinations from the official label. Rates converted to per-acre. PHI is the pre-harvest interval; REI is the restricted-entry interval. Always confirm against the official label PDF before applying.
| Crop | Target | Rate | PHI | REI |
|---|---|---|---|---|
| Air Washers and Industrial Scrubbing Systems | Microorganisms | 333–1300 ppm | – | – |
| Air Washers and Industrial Scrubbing Systems | Microorganisms | 100–333 ppm | – | – |
| Drilling Muds | Microorganisms | 170–3330 ppm | – | – |
| Drilling Muds | Microorganisms | 170–3330 ppm | – | – |
| Gas Production and Transmission Pipelines and Systems | Microorganisms | 1670–16670 ppm | – | – |
| Gas Storage Wells and Systems | Microorganisms | 1670–16670 ppm | – | – |
| Gas Storage Wells and Systems | Microorganisms | 670–6670 ppm | – | – |
| Heat Transfer Systems | Microorganisms | – | – | – |
| Hydrotesting | Microorganisms | 330–13330 ppm | – | – |
| Industrial Wastewater Systems | Microorganisms | 1.5–7.5 L/1000L | – | – |
| Packer Fluids | Microorganisms | 170–2000 ppm | – | – |
| Paper Mills | Bacteria including slime-forming bacteria, sulfate-reducing bacteria, fungi, yeast and algae | – | – | – |
| Paper Mills | Bacteria including slime-forming bacteria, sulfate-reducing bacteria, fungi, yeast and algae |
| – |
| – |
| – |
| Pigments and Filler Slurries | Microorganisms | – | – | – |
| Pipeline Pigging and Scraping | Microorganisms | 0.3–3.3 % | – | – |
| Recirculating Cooling and Process Water Systems | Microorganisms | 333–1300 ppm | – | – |
| Recirculating Cooling and Process Water Systems | Microorganisms | 50–333 ppm | – | – |
| Service Water and Auxiliary Systems | Microorganisms | – | – | – |
| Water Floods | Microorganisms | 330–16670 ppm | – | – |
| Water Floods | Microorganisms | 67–16670 ppm | – | – |
| Water-Based Coatings | Microorganisms | – | – | – |
About this content. This page presents the official PRD label as published by Health Canada's Pesticides Regulatory Directorate (formerly the Pest Management Regulatory Agency), the source of record. Always read the official label and consult your provincial pesticide- application authority before use. Report an error.